Description
ENTRANCE
NEMA → 5-15P
Nominal voltage → 220 VAC
Voltage range → 55/150 VAC ± 5% or ± 5% at 50% load
Frequency Range → 80/150 VAC ± 5% or ± 5% at 100% load 40Hz ~ 70 Hz
Phase → Single phase with grounding
Power factor → ≧ 0.99
EXIT
NEMA → (4 Nemas) 5-15/20R
Output voltage → 220 VAC
AC voltage regulation (Battery Mode) → ± 1%
Frequency range (Synchronization range) → 48~52Hz or 58~62Hz
Frequency Range (Battery Mode) → 50Hz ± 0.2Hz or 60Hz ± 0.2Hz
Current peak range → 3:1
Harmonic Distortion (Line Mode) → ≤3% (Load Line)
Wave type (Battery mode) → Pure sine wave
EFFICIENCY
AC mode → 88.2%
ECO mode → 94%
Battery Mode → 84.6%
BATTERY
STANDARD MODEL
Battery type → 12 V / 7 Ah
Numbers → 3
Typical recharge time → Recovery in 4Hrs to 90% of its capacity
Charging current (max.) → 1.0 A
Current voltage → 41.1 VDC ±1%
LONG-RUN MODEL
Battery type → Depending on your application
Numbers → 3
Charging current (max.) →1A
Current voltage → 41.1 VDC ±1%
INDICATORS
LCD Panel → UPS status, load level, battery level, input/output voltage, discharge timer, and fault conditions
ALARM
Battery mode → Ringing every 4 seconds
Low battery → Beeping every second
Overload → Beeping twice every second
Criticism → Continuously ringing
PHYSICAL CHARACTERISTICS
STANDARD MODEL
Dimensions. DxWxH(mm) → 510 x 438 x 88
Net weight (kgs) → 18.4
LONG RUN MODEL
Dimensions. DxWxH(mm) → 510 x 438 x 88
Net weight (kgs) → 11.3
OPERATING ENVIRONMENT
Relative humidity → 20-90% RH @ 0-40°C (Non-condensing)
Noise level → Less than 50 dB at 1 meter
MANAGEMENT
Smart RS-232/USB → Supports Windows 2000/2003/XP/Vista/2008,Windows 7/8, Linux,Unix, and MAC
Default policy → UPS monitoring and management, via SNMP over the Internet.