Description
- IDNAC SLC controlled advanced addressable notification providing regulated 29 VDC allowing strobes on the same SLC to operate at lower current even with battery backup.
- Wiring supervision for each appliance allows for “T-tap” connections for Class B circuits to simplify wiring (Class A circuits require input/output wiring).
- Self-test mode allows a built-in sensor to detect the horn output and then report its status to the control panel.
- The horns are controlled separately from the visible fixtures on the same SLC with control panel operation selection as: Temporal Code 3, Run Time (selectable as 20, 60 or 120 bpm), Continuous or Temporal Code 4.
- “High” or “low” output (~6 dBA difference) selectable at the device or from the controller with FACP mode selected on the device.
- Listed to UL Standard 464 and ULC Standard S525.