Description
| Communications | IDNet or MAPNET II, 1 address per device |
| ZAM input voltage | 18.9 to 32 VDC (24 VDC nominal) |
| ZAM current at 24 VDC |
(actual current is determined by total device requirements) |
| Zone Supervision Resistor, ZAM 4090-9101 | 3.3 kΩ, 1 W |
| Wiring connections | Screw terminals for input and output wiring, AWG 18 to 14 AWG (0.82 to 2.08 mm2) |
| IDNet or MAPNET II wiring | Up to 2500 feet (762 m) from fire alarm control panel |
| Up to 10,000 feet (3048 m) total wiring distance (including T-Taps) | |
| Compatible with Simplex surge protectors 2081-9044 | |
| Dimensions | 4” high x 4” wide x 1 ⅜” deep (105mm x 105mm x 35mm) |
| Housing material | Black thermoplastic |
| End Plate Material | Sheet metal, galvanized |
| Temperature range | 32° to 120° F (0° to 49° C) intended for indoor operation |
| Humidity range | Up to 93% RH, at 100° F (38° C) |