SIMPLEX 4090-9101 MBZAM Zone Adapter Module

Save 9%

Price:
Sale priceS/. 195.00 PEN Regular priceS/. 215.00 PEN
VER FICHA TÉCNICA
Contact us

Description

Communications IDNet or MAPNET II, ​​1 address per device
ZAM input voltage 18.9 to 32 VDC (24 VDC nominal)
ZAM current at 24 VDC
  • Supervision = 16 mA maximum
  • Alarm = 72 mA maximum

(actual current is determined by total device requirements)

Zone Supervision Resistor, ZAM 4090-9101 3.3 kΩ, 1 W
Wiring connections Screw terminals for input and output wiring, AWG 18 to 14 AWG (0.82 to 2.08 mm2)
IDNet or MAPNET II wiring Up to 2500 feet (762 m) from fire alarm control panel
Up to 10,000 feet (3048 m) total wiring distance (including T-Taps)
Compatible with Simplex surge protectors 2081-9044
Dimensions 4” high x 4” wide x 1 ⅜” deep (105mm x 105mm x 35mm)
Housing material Black thermoplastic
End Plate Material Sheet metal, galvanized
Temperature range 32° to 120° F (0° to 49° C) intended for indoor operation
Humidity range Up to 93% RH, at 100° F (38° C)