Description
Flushing systems require maintenance disconnect switches and often require abort switches. These maintenance and interruption switches are clearly labeled and combine easy operation with rugged construction for high integrity operation.
Abort switches provide 2080-9057 a request for manual release abort of the fire suppression system:
- The momentary push button switch is mounted on a single gang stainless steel plate
- A protruding collar protects the switch from accidental contact (collar can be removed if necessary)
- Flush or surface mounting available
- Flush mounting requires a standard single-gang box
- Surface mount includes a red mounting box
- Models are available with a 1.2 kΩ internal resistor for current-limiting operation.
SPECS
| Cancel switch | Silver contacts; 1 NO & 1 NC; Rated 2 A resistive @ 30 VDC |
| Maintenance switch control Contact block (all models) |
Circuit control: silver contacts; 1 normally open and 1 normally closed; rated 2 A resistive @ 30 VDC |
| Maintenance switch lamp contact block |
Lamp Control: Silver plated contacts; 1 normally open and 1 normally closed; rated 2 A resistive @ 30 VDC |
| Maintenance switch indicator light | Replaceable 2 W incandescent bulb; 24 to 30 VDC typical; 83 mA at 24 VDC; requires separate 24 VDC |
Wiring connections
| Cancel switch | Terminal blocks for input/output wiring; 18 to 14 AWG (0.82 mm2 to 2.08 mm2) wire |
| Current-limiting resistor abort switch | Terminal blocks for first wire connection; 18 to 14 AWG (0.82 mm2 to 2.08 mm2); 18 AWG lead wire for second wire connection. |
| Maintenance switch | 18 AWG (0.82 mm2) color-coded lead wires, for suppression circuit; terminal blocks for lamp wiring; 18 to 14 AWG (0.82 mm2 to 2.08 mm2) wire |
| Additional information | 579-416, Installation Instructions |
Environmental Ratings
| Temperature range | 32°F to 120°F (0°C to 49°C) |
| Humidity range | Up to 93% at 90°F (32°C) |