Description
The RE-25AR UL listed microprocessor based agent release panel has dual function of gaseous agent detection and release. The system has 16X2 characters LCD, 4 zone detection circuit and 2 main agent release circuits, it has various programmable logic options, the system has RTC function, Auto and manual operation function, Solenoid output with ON and OFF timer with solenoid coil monitoring function, programmable main output facility, gas use and instant release, manual release with time delay or without time delay and low pressure detection facilities. Switching power supply - SMPS, Battery polarity and deep discharge protection.
SPECS
Primary power supply (RE-SMPS-4A-R1) | 120 – 220 VAC ± 10%, 50 Hz, 2.5 Amps. | |
Backup power | 24v DC (2 numbers of 12v, 12Ah sealed lead acid battery). | |
Quiescent current | 120 mA. | |
Operating conditions | Operating Operating temperature 0 – 49° C / 32-120° F. | |
Relative humidity 93 ± 2% RH (non-condensing) at 32±2° C / 90 ± 3° F. | ||
Charging circuit | Voltage charge | 28.0V, ± 0.2V |
Current load | 800mA (Max). | |
DC output power | Supervised 24VDC regulated, 300mA. | |
Common relays | Guy | Shape C |
Number of relays | 3 | |
Relay contact classification | 2 Amps @ 30 VDC, | |
Programmable input circuits | Number of entries | 4 |
Normal operating voltage | 8 – 12 VDC. | |
Short circuit current | 5 mA maximum. | |
Loop resistance | 100 ohms maximum. | |
End of line resistor | 3K9, 1/2 watt | |
Standby current | 2.5 mA. | |
Maximum manual release switch | 3 numbers. | |
Initiating Device Circuits | All zones are Class B Style B/C operation (Programmable). | |
Normal operating voltage | 14 – 21 V DC. | |
Alarm current | 15 – 30mA. | |
Short circuit current | 45 mA maximum. | |
Loop resistance | 100 ohms maximum. | |
End of line resistor | 3K9, 1/2 watt | |
Standby current | 7 mA (2 mA for detectors) | |
Notification appliance circuits | Class B Wiring, Style – Y | |
Number of circuits | 2 | |
Operating voltage | 24V DC. | |
Nominal current | 0.6 A per circuit | |
Line drop | 1.8V | |
End of line resistor | 3K9, 1/2 watt | |
Releasing agent circuits | Releasing agent circuits | |
Number of circuits | 2 | |
Operating voltage | 24 V DC. | |
Nominal current | 0.6 A per circuit | |
Line drop | 1.8V | |
End of line resistor | 3K9, 1/2 watt |