Description
Initial description
FPD-7024 Fire Alarm Control Panels (FACP) can be used in commercial and public applications such as schools, universities, manufacturing plants, and healthcare facilities. They are UL certified for central, local, auxiliary, and remote station systems.
Four detector zones (expandable to eight); up to 20 two-wire smoke detectors per zone.
The FPD-7024 FACPs support four built-in initiating zones that can be expanded to eight using the FPC-7034. Each initiating zone supports two- and four-wire detectors that can be configured as Class A, Style D or Class B, Style B circuits. Each zone supports up to 20 two-wire detectors, or any number of four-wire detectors depending on available power. Each FACP features an integrated Digital Fire Alarm Communicator Transmitter (DACT).
Enhance the features of your conventional FPD-7024 system by adding an FPE-7039 Multiplex Expansion Module. Adding an FPE-7039 Multiplex Expansion Module to the FPD-7024 converts the conventional FACP into an addressable FACP. The FPE-7039 adds up to 247 addressable points to the base system and an additional 400 events in the history buffer for a total of 499 events. The FPE-7039 It also increases the number of programmable relay outputs from 19 to 59 and extends the system users to 100.
Features and Specifications
Main Features
- Four initiation zones (expandable to eight); up to 20 two-wire smoke detectors per zone.
- Programmable via numeric keypads or Remote Programming Software (RPS) through a Conettix interface module.
- Two integrated Notification Appliance Circuits (NAC) with a shared, regulated internal 24 VFWR, 4 A NAC power supply.
- Easily becomes addressable with the addition of a FPE-7039 multi-expansion module
Specs
Electrical
- Current (alarm)*: 380 mA
- Current (standby)*: 200 mA
- Power (primary): 120 VAC, 1.2 A maximum, 60 Hz or 240 VAC, 0.75 A maximum, 50 Hz.
Environmental
- Environment: Indoor, dry
- Relative humidity: Up to 95%, non-condensing
- Temperature (operating): +32°F (0°C) to +120°F (+49°C).
Mechanics
- Red
- Dimensions (H x W x D) 20.8 in. x 15 in. x 4.3 in. (52.8 cm x 38.1 cm x 10.9 cm).
- Material: Cold rolled steel.
- Base: 18 gauge (1.2 mm).
- Cover: 19 gauge (1.1 mm).
Indication Device Circuits (IDC)
- Current: 44 mA maximum per circuit.
- Line resistance: 150 Ω.
- Voltage: 24 VDC nominal.
Departures
NAC: 24 VDC nominal, 4 A maximum
- Integrated Relays: Three Form C contacts rated at 5 A, 28 VDC.
- External Relays: Up to two D7035 octal relay modules each providing eight Form C relay outputs, contacts rated at 5 A, 28 VDC. In the addressable system, up to 20 D7053 multiple input/output modules are allowed per module. bus for a total of 40.