Description
The MIX-4050 synchronization module is designed for use with MGC Alarm Notification devices. The synchronization module is used to synchronize the flashing of the strobes with the audio signal pattern. The same protocol is used to silence the horn while maintaining the strobe flashes. It also supports the two-stage alarm function, Alert (20 beats per minute) and Evacuation (Temporal Pattern 3).
The synchronization module is installed between a fire alarm system NAC circuit and alarm notification appliances. When there is no alarm, the NAC line connected to the synchronization module is off and no power is applied to the device. When the NAC line is turned on, the device is powered up and becomes operational. Up to 20 modules can be interconnected to achieve synchronization without the need to program or select a master unit. An LED will indicate activation and master/slave status. The master will flash intermittently while the slave will flash rapidly. Proper interconnection of devices can be verified by ensuring that only one device is flashing at the master rate.
The mute input can be used to mute the NAC devices on a MIX-4050 without affecting the other MIX-4050 devices that are interconnected. The module can synchronize one (1) Class A NAC line or two (2) Class B NAC lines without the need for programming. This is a hardware-only device and does not require programming or setting of switches or jumpers.
Characteristics
- The sync module does not consume current in idle state.
- No addressing required.
- An LED indicates activation and master/slave status.
- The Sync Module is compatible with any UL/ULC listed panel and power supply capable of providing 24 VDC regulated or full wave rectifier FWR for NAC circuits.
- Interconnected MIX-4050 modules automatically synchronize without the need for programming or configuration jumpers.
Specs
| Operating voltage | 24 VDC Regulated (16 to 33 VDC Filtered or FWR) |
| Alarm Supply Current | Maximum 25mA average |
| Current Alarm Notification Circuit NAC | 3A for class A circuit, 2 x 3A for class B circuit |
| Input trigger voltage | First Stage and Mute 16 to 33 VDC Filtered or FWR |
| Input trigger current | First Stage and Mute Maximum 3.5 mA. @ 33 VDC |
| Synchronous Circuit | Current and voltage limited internally |
| Temperature Range | 32°F to 120°F (0°C to 49°C) |
| Humidity | 10% to 93% Non-condensing |
| Dimensions | 4.625 inches High x 4.25 inches Wide x 1.125 inches Depth |
| Mounting | 4” x 2 1/8” Square Electrical Box depth |
| Gauge of conductors at all terminals | 22 to 12 AWG |