MIRCOM MIX-4042 Zone module for FX400 series

Save 20%
SKU: MIX-4042
No reviews

Price:
Sale priceS/. 301.00 PEN Regular priceS/. 375.00 PEN

Shipping calculated at checkout

Stock:
In stock
VER FICHA TÉCNICA

Description

The MIX-4042 analog interface module is designed to be used with a compatible MGC control panel providing high, reliable and secure data exchange rates.

The MIX-4042 Conventional Zone Module allows a zone of conventional detectors to be connected to an intelligent SLC loop. It can also be configured to operate with sensors with a 4-20 mA output signal.

A listed external power supply can be connected to multiple MIX-4042 modules to provide power to the devices while remaining electrically isolated from the fire alarm control panel. Each MIX-4042 module monitors the current drawn by the devices and reports the alarm or trouble condition accordingly.

When configured for conventional devices, the module will automatically handle Class A or Class B circuits. When the MIX-4042 is configured for Class A operation, the module provides an internal EOL resistor. An MP-300 end-of-line resistor must be used for applications with Class B wiring.

Characteristics

  • Up to 240 MIX-4000 Series devices can be connected in any combination, on a single SLC signaling loop.
  • Mounts in standard 4 inch electrical gang box or double gang rectangular electrical gang box.
  • The indicator LED provides the status of the module.
  • Compatible with conventional alarm initiating devices or sensors with a two-wire 4-20 mA signal.
  • The IDC alarm initiating circuit can be configured to operate as one (1) Class A circuit or one (1) Class B circuit with conventional devices.

Specs

SLC Signaling Loop Specifications
Normal Operation Voltage 15 to 30 VDC
Normal operating current 1.6mA
Current in Alarm 3.0mA
Device specifications
End of Line Resistor EOL (Conventional Zone) 3900 Ohms
Maximum Wiring Resistance (4-20mA) 200 Ohms
Max. Wiring Resistance (Conventional Zone) 100 Ohms
External Power Supply (Voltage) Nominal Voltage 24 VDC, (18 to 30 VDC)
External Power Supply (Current) Maximum current 23 mA maximum at 30 VDC (EOL only)
EOL Current (Conventional Only) 5mA maximum
Current Conventional Devices 3mA total or less
Maximum Short Circuit Current 70mA (55mA on device wiring)
Temperature Range 32ºF to 120ºF (0ºC to 49ºC)
Humidity 10% to 93% No condensation
Wire Gauge Range on Terminals 22 to 12 AWG
Dimensions 4.625 inches High x 4.25 inches Wide x 1.125 inches
Depth
Mounting Typically mounted in 4" square electrical box. Can also be mounted in double rectangular electrical box or Mircom B-400 surface mount electrical box.