The MIX-4040-M multi-input module is an intelligent addressable device that can be used for alarm, monitor, or supervisory type applications. It is designed to be used with an MGC compatible fire alarm control unit. The MIX-4040 -M provides six (6) Class A or twelve (12) Class B inputs. If the module is configured as Class A, it provides an internal EOL and when configured as Class B, the module can monitor 12 inputs with a single address.

The MIX-4040-M address is configured using the MIX-4090 handheld programming tool. The module has LED indicators for each input to indicate alarm (RED) or trouble (YELLOW). A green LED displays the SLC communication status. and finally, two yellow LEDs indicate if a short has been isolated on either side of the SLC connection.

The MIX-4040-M provides fast and quick installation as it comes with plug-in terminal blocks and can be easily mounted on DIN rail without using any additional tools. The MIX-4040-M can be mounted on the BB-4002R, which supports up to 2 multi-modules, or the BB-4006R, which allows up to 6 multi-modules. The MIX-4040-M can also be mounted on any UL/ULC listed back box using the mounting bracket kit.

Characteristics

  • Supports 6 Class A or 12 Class B inputs.
  • No EOL resistor is required when the input is in Class A operation.
  • Monitors 12 independent input circuits with a single address when configured as Class B
  • Fast and reliable contact monitoring
  • Affordable and space saving
  • DIN rail mounting clip and plug-in terminal blocks for quick and easy installation
  • Each input has LED indicators to signal Alarm (RED) or Trouble (YELLOW)
  • Additional LEDs to show the SLC communication status and whether a short circuit has occurred
  • Compatible with FX-400, FX-401 and Flex-Net FX-4000 fire alarm control panels
  • Up to 2 modules can be mounted in the UL/ULC listed back box, BB-4002R
  • Up to 6 modules can be mounted in the UL/UL listed back box, BB-4006R
  • Mounting bracket kit allows mounting to any other equivalent UL/ULC listed junction box

Specs

Normal operating voltage 15 to 30 VDC
Alarm current 8.3 mA
Standby current: 4.0 mA max.
EOL resistance 22 kΩ
Maximum input wiring resistance: 150 Ω in total
Operating temperature range: 32°F to 120°F (0°C to 49°C)
Humidity range 10% to 93% non-condensing
Dimensions 110mm x 93mm (4 5/16 x 3 11/16 inches)
Wiring range on all terminals 12-22 AWG