- Listed to UL 864, 9th Edition.
- 8 Class B (Style B) initiator circuits that can be configured as 4 Class A (Style D) circuits.
- Expandable up to 24 Class B or 12 Class A initiating circuits.
- 4 Class A/B (style Z/Y) indicating circuits with individual trouble indicators (1.7 amps max per circuit).
- Each indicator circuit can be configured as silenceable or non-silenceable. Audible signals can be configured as constant, time code, California code, or running time.
- Each initiating circuit can be configured as alarm, supervisory, waterflow, or trouble.
- Two LEDs per starter circuit; one for trouble and one for status
- The initiation and indication circuits can be individually switched off using a DIP switch.
- Configurable signal silence inhibition, automatic signal silence, two-stage operation and one-person walk test.
- Alarm verification in initiation circuits.
- Post-alarm operation, monitoring and troubleshooting.
- Two 4-wire resettable smoke power supply outputs (200 mA max each).
- Auxiliary relay contacts for common alarm and common supervisory, as well as a common trouble relay (each Form C relay contact, 28 VDC at 1 A (resistive)).
- RS-485 interface for RA-1000 multiplex remote annunciators.
- Interface for remote problem indicator.
- Easy configuration via push buttons and DIP switches on the front panel.
- Wide transient protection.
- 6A power supply.
Applications
Mircom's FA-1008KADS is designed as a cost-effective microprocessor-based fire alarm control unit that can be expanded up to 24 display points. Its modular design accommodates a variety of applications. Ideal for applications such as small institutional and commercial buildings, Whether it's shopping malls, offices or public facilities, the FA-1008KADS can be configured to meet virtually any requirement. The unit is designed for easy installation, operation and maintenance. This makes the system cost effective and highly reliable for applications planned.