Description
He KI-HFD by KIDDE It is a fixed temperature smart detector and contains a sensor that is activated when it detects 135°F (57.2°C). It does not have an incremental temperature function. The heat sensor monitors the temperature of the air in its surroundings and analyzes the data to determine when the temperature will not exceed the device's alarm point.
KI Series smoke detectors bring advanced detection technology to a practical design that increases efficiency, saves installation time, reduces costs, and extends life safety and property protection. Continuous self-diagnostics ensure long-term reliability, while the latest determistor technology makes these detectors ideal wherever reliable heat detection is required.
Characteristics
| Operating voltage | 15.20 to 19.95 VDC |
| Normal operating current | 51 microA |
| Alarm operating current | 68 microA |
| Maximum spacing [1] | 50 feet (15.2 m) centers |
| Operating Environment Temperature Relative Humidity | 32 to 100°F (0 to 38°C) |
| 0 to 93% non-condensing | |
| Storage temperature | 4 to 140°F (20 to 60°C) |